Tytuł pozycji:
Synchronous generator for induced AC voltage test of single-phase and three-phase power transformers
The paper presents the method of selection, calculation and measurements of generator that is built into the new transformer test station. The three phase cylindrical synchronous generator 800 kVA, 200 Hz with special damper bars is most suitable to be used as a power supply for testing of single-phase and three-phase power transformers. The emphasis is on the analysis of the armature winding connection and sizing of the damper winding due to unsymmetrical load of a generator in the induced AC voltage test. The results indicate that D-connected generator with skewed stator slots is the best solution. Special temperature sensors were mounted in the rotor.
W artykule przedstawiono metodę wyboru, obliczeń oraz pomiarów generator wbudowanego w nową transformatorową stację badawczą. Trójfazowy cylindryczny generator trójfazowy o mocy 800 kVA i częstotliwości 200 Hz ze specjalną szyną tłumiącą jest najdogodniejszy jako urządzenie zasilające do prób transformatorów jedno- i trójfazowych. Szczególną uwagę zwrócono na połączenie uzwojeń i wielkość uzwojenia tłumiącego z powodu niesymetrycznego obciążenia generatora w przypadku próby indukowanym napięciem. Wyniki wskazują na to, że generator z uzwojeniami połączonymi w trójkąt i skoszonymi żłobkami statora jest rozwiązaniem najlepszym. Specjalne czujniki temperatury zostały zamontowane w wirniku.