Tytuł pozycji:
Determination of salient pole synchronous machines electromagnetic parameters from the SSFR test
Presented article deals with the determination of hydrogenerator electromagnetic parameters from the SSFR test. A method utilized to prepare the results is finite element method based on the module of Steady State AC Magnetic 2D application. Obtained reactances could be determined after an application of own made program used to fit the curves (magnitude and phase characteristic of operator transmittances) to the data coming from the simulation in order to designate the time constants. An impact of saturation effect in stator and rotor steels was researched on obtained reactances in different working states of synchronous machine.
Prezentowany artykuł przedstawia symulacyjną metodę wyznaczania parametrów elektromagnetycznych hydrogeneratora z testu SSFR (Standstill Frequency Response). Zastosowana metoda obliczeń bazuje na rozkładzie pól sinusoidalnie zmiennych o zadanej zmiennej częstotliwości. Reaktancje hydrogeneratora zostały wyznaczone ze stałych czasowych za pomocą opracowanego programu. Program ten dopasowuje charakterystyki amplitudowe i fazowe do wartości otrzymanych z symulacji. Zbadano wpływ nasycenia obwodu magnetycznego na reaktancje odzwierciedlające zachowanie maszyny w różnych stanach pracy.
Opracowanie rekordu w ramach umowy 509/P-DUN/2018 ze środków MNiSW przeznaczonych na działalność upowszechniającą naukę (2019).