Measurement point density and measurement methods in determining the geometric imperfections of shell surfaces

Tytuł:
Measurement point density and measurement methods in determining the geometric imperfections of shell surfaces
Autorzy:
Kocierz, R.
Rębisz, M.
Ortyl, Ł.
Data publikacji:
2018
Słowa kluczowe:
cooling towers
geometrical imperfection
minimal point density
deformation
wieże chłodnicze
niedoskonałość geometryczna
gęstość punktów
odkształcenie
Język:
angielski
Dostawca treści:
BazTech
Artykuł
  Przejdź do źródła  Link otwiera się w nowym oknie  Pełny tekst  Link otwiera się w nowym oknie
In geodetic measurements of deformations in shell cooling towers, an important factor is to optimize the number of points representing the exterior surface of the shell. The conducted analyses of damage to such structures proved that cooling towers exhibited shell deformation consisting of irregular vertical waves (three concavities and two convexities), as well as seven horizontal waves. On this basis, it is claimed that, in accordance with the Shannon theorem, the correct representation of the generated waves requires the measurement of the cooling tower shell in a minimum of 12 vertical and 14 horizontal sections. Such density of the points may not be sufficient to represent local imperfections of the shell. The article presents the results of test measurements and their analysis, which were conducted to verify the assumptions as to the optimal number of measurement points for the shell of a cooling tower. The evaluation was based on a comparative analysis of the data obtained by the Terrestrial Laser Scanning (TLS) method, creating a very detailed model of geometric imperfections in an actual cooling tower with a height of 100 m. Based on the data obtained by the TLS method, point grids of various density were generated. An additional measurement of the cooling tower shell deformation was performed using a precise electronic total station with reflectorless measurement option. Therefore, it was possible to assess the accuracy of measurements by laser scanning in relation to measurements obtained by reflectorless total stations.
Opracowanie rekordu w ramach umowy 509/P-DUN/2018 ze środków MNiSW przeznaczonych na działalność upowszechniającą naukę (2018).

Ta witryna wykorzystuje pliki cookies do przechowywania informacji na Twoim komputerze. Pliki cookies stosujemy w celu świadczenia usług na najwyższym poziomie, w tym w sposób dostosowany do indywidualnych potrzeb. Korzystanie z witryny bez zmiany ustawień dotyczących cookies oznacza, że będą one zamieszczane w Twoim komputerze. W każdym momencie możesz dokonać zmiany ustawień dotyczących cookies