Tytuł pozycji:
Breakdown and acceleration voltage of biodegradable liquid made in GTL technology at positive lightning impulse voltage
This paper compares the lightning properties of the inhibited biodegradable insulating fluid produced using Gas-to-Liquids (GTL) technology, which was designated GTL-I-BIO, with conventional transformer fluids such as uninhibited mineral oil (UMO) and synthetic ester (SE). The comparative analysis was performed for two parameters: lightning impulse breakdown voltage (LIBV) and acceleration voltage (Va). The tests were performed at the standard lightning impulse voltage under positive polarity for two inter-electrode gaps: 25 mm and 40 mm. The highest LIBV value was recorded for UMO. However, the highest Va value was obtained by GTL-I-BIO.
W artykule porównano właściwości udarowe inhibitowanego biodegradowalnego płynu izolacyjnego wytworzonego w technologii Gas-to-Liquids (GTL), który oznaczono GTL-I-BIO, z konwencjonalnymi cieczami transformatorowymi, takimi jak nieinhibitowany olej mineralny (UMO) i ester syntetyczny (SE). Analizę porównawczą przeprowadzono dla dwóch parametrów: udarowego napięcia przebicia (LIBV) i napięcia przyspieszenia (Va). Badania przeprowadzono przy udarowym napięciu piorunowym normalnym o biegunowości dodatniej, dla dwóch odległości międzyelektrodowych: 25 mm i 40 mm. Najwyższą wartość LIBV odnotowano dla UMO. Natomiast najwyższą wartość Va, uzyskał GTL-I-BIO.
Opracowanie rekordu ze środków MNiSW, umowa nr POPUL/SP/0154/2024/02 w ramach programu "Społeczna odpowiedzialność nauki II" - moduł: Popularyzacja nauki i promocja sportu (2025).